Fuels - Suitable for kerosene, No. 1 or No. 2 Fuel Oil | |
| Startup - can be manually bled or primed during start up | |
| Operation - Requires fuel unit to provide vacuum to open and make fuel available | |
| Provides - Protection for line break |
| Model | Temperature Range | Maximum Flow | Max. Inlet Pressure | Ports |
| PRV-38 | 0 to 160 F | 55 gph | 40 psi | 3/8" NPT |
|
Flow Through Valve (GPH) |
Inlet Pressure (PSI) |
|||
| 5 psi | 15 psi | 30 psi | 40 psi | |
| 1 | 3.2 | 3.4 | 4.1 | 4.9 |
| 5 | 3.3 | 3.6 | 4.3 | 5.1 |
| 15 | 3.6 | 4.1 | 4.7 | 5.5 |
| 25 | 4.0 | 4.5 | 5.1 | 5.8 |
| 35 | 4.4 | 4.9 | 5.6 | 6.2 |
| 45 | 4.7 | 5.3 | 6.0 | - |
| 55 | 5.3 | 6.0 | - | - |